40.5kV T-Connector Front Plug

Product Descriptions
  • Premolded stress cone with geometric design and combine with sufficient interface pressure ensures effective electric field control and long-term reliability;

  • With sufficient electrical margin;

  • Installation requires no specialized tools, heating, or filling;

  • Can be installed vertically, at an inclined (≤30°) position;

  • Can be energized immediately after installation.

Contact us

Product Details

Application

• Connects cables to electrical cabinet or transformer.


Compatible Cables

• Cable Type: XLPE or other polymer-insulated, single or three cores copper/aluminum conductor MV power cables; 

• Metallic Screen: Steel tape, Copper tape, Copper wires, Al wires, Al foil tape and etc.

 

Product Application Standards

• Applicable standards: IEC 60502-4,GB/T 12706.4; 

• Interface standard :EN50180 - EN50181.


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

26/35 (40.5) kV

Rated Voltage (U₀ / U)

26/35kV

Highest System Voltage (Uₘ)

40.5 kV

Partial Discharge Test (pC)

At 1.73 U0 : no detectable PD above specified sensitivity

Power Frequency Withstand Voltage (KV)

At 4.5 U0 for 5 min, no breakdown or flashover

Lightning Impulse Level(KV)

200

Pollution Level

Height( mm)

350

Net Weight (Excluding Cable) ( kg)

~3.5

 

Optional Solutions
• The connection between the cable lug and the cable conductor employs crimping or mechanical methods; 

• The length of the grounding wire can be customized.


Operating Conditions
• Ambient Temperature: -45°C to 45°C

• Installation altitude: no limitation.


Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Indoor with dry and clean environment, keepsealing and avoiding >=4 layers overlap.

Available Termination Selection (Recommended by Cable Insulation Diameter

Voltage Level(kV)

Product Type

Conductor Size Range(mm²)

Cable Insulation Diameter(mm)

26/35/40.5

CBQ10-C-26/35-1x50~120

50~120

30.9~52.6

26/35/40.5

CBQ10-C-26/35-1x150~300

150~300

37.2~43.2

26/35/40.5

CBQ10-C-26/35-1x400~630

400~630

46.4~52.6

26/35/40.5

CBQ10-C-26/35-3x50~120

50~120

30.9~52.6

26/35/40.5

CBQ10-C-26/35-3x150~300

150~300

37.2~43.2

26/35/40.5

CBQ10-C-26/35-3x400~630

400~630

46.4~52.6

Note:If the Termination's specification is outside the above ranges can be customized based on cable section and insulation diameter.