36kV Cold Shrinkable Straight Joint

Product Descriptions
  • The premolded stress cone, designed using geometrical electric field control and combine with sufficient interface pressure, ensures uniform electric field distribution and long-term reliable operation;

  • With sufficient electrical margin;

  • Have excellent sealing performance with armor tape as normalMature design with long-term successful service experience.

Contact us

Product Details

Application

• Designed for the connection of MV power cables.

• Suitable for underground tunnels, direct burial installations (protective box recommended), and installation on cable racks or supports.

• Applicable for connecting different cable cross-sections within a certain range of MV cable systems.


Compatible Cables

• Cable type: : XLPE or other polymer-insulated, single or three cores MV power cables; 

• Metallic Screen: Copper tape, Copper wires, Al wires, Al foil tape and etc


Product Application Standards

• Applicable standards: IEC 60502-4,GB/T 12706.4


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

18/30 (36) kV

Rated Voltage (U / U)

18/30kV

Highest System Voltage (U)

36kV

Partial Discharge Test (pC)

At 1.73 U: no detectable PD above the specified sensitivity

Power Frequency Withstand Voltage (KV)

At 4.5 U for 5 min, no breakdown or flashover

Lightning Impulse Withstand Voltage

170

Overall Dimensions (L × Ø)

520*81

Net Weight (excluding cable)

15

 

Optional Solutions

• The connector between cable conductors could be crimp or mechanical type.

• Optional protective box according to installation conditions;

• Sectionalized Joint design can be used for longer circuit with outer earthing system.


Operating Conditions

• Ambient temperature: –45 °C to +45 °C

• Installation altitude: No limitation.


Storage Conditions

• Optimal Storage Temperature: 10°C to 25°C
• Indoor with dry and clean environment, keep sealing and avoiding ≥4 layers overlap.

Straight-Through Joint Selection Guide(Recommended selection based on cable insulation diameter)

Voltage Level (kV)

Product Type

Conductor   Size Range (mm²)

Cable   Insulation Diameter (mm)

Protective   Housing

18/30/36

JLS-18/30-1x50~120

50~120

30.9~52.6

W/O protective   housing

18/30/36

JLS-18/30-1x150~300

150~300

37.2~43.2

18/30/36

JLS-18/30-1x400~630

400~630

46.4~52.6

18/30/36

JLS-18/30-3x50~120

50~120

30.9~52.6

18/30/36

JLS-18/30-3x150~300

150~300

37.2~43.2

18/30/36

JLS-18/30-3x400~630

400~630

46.4~52.6

Note:If the Termination's specification is outside the above ranges can be customized based on cable section and insulation diameter.