Premolded stress cone with geometric design and uniform interfacial pressure from the spring compression system ensures effective electric field control and long-term reliability;
With sufficient electrical margin;
Installation requires no specialized tools, heating, or filling;
It can be installed vertically, at an incline (≤30°), or inverted;
It can be energized immediately after installation.
Application
• Connects cables to overhead lines/copper busbars.
Compatible Cables
• Cable Type: XLPE or other polymer-insulated, single-core copper/aluminum conductor MV power cable.
• Metallic Screen: Copper tape, Copper wires, Al wires, Al foil tape and etc.,
Product Application Standards
Applicable standards: IEC 60502-4,GB/T 12706.4.
Technical Parameters
| Item | Technical Specifications |
Voltage Level(kV) | 18/30 (36) kV |
Rated Voltage (U₀ / U) | 18/30kV |
Highest System Voltage (Uₘ) | 36kV |
Partial Discharge Test (pC) | At 1.73 U₀: no detectable PD above specified sensitivity |
Power Frequency Withstand Voltage (KV) | At 4.5 U₀ for 5 min, no breakdown or flashover |
Lightning Impulse Level(KV) | 170 |
Creepage Distance ( mm) | ≥1015 |
Pollution Level | Ⅳ |
Height( mm) | 680 |
Net Weight (Excluding Cable) ( kg) | ~2.0 |
Optional Solutions
• Products with increased creepage distance for high-altitude areas;
• The lug between the cable and terminal could be crimp or mechanical type.
Operating Conditions
• Ambient Temperature: -45°C to 45°C
• Installed indoor or inside electrical cabinet;
• Installation altitude: ≤ 2000 meters (For higher altitude areas, bigger creepage distance should be selected based on the specific conditions).
Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Indoor with dry and clean environment, keep sealing and avoiding ≥4 layers overlap.
Available Termination Selection (Recommended by Cable Insulation Diameter
Voltage Level(kV) | Product Type | Conductor Size Range(mm²) | Cable Insulation Diameter(mm) |
18/30/36 | NLS- 18/30-1x50~120 | 50~120 | 30.9~35.6 |
18/30/36 | NLS- 18/30-1x150~300 | 150~300 | 37.2~43.2 |
18/30/36 | NLS- 18/30-1x400~630 | 400~630 | 46.4~52.6 |
Note:If the Termination's specification is outside the above ranges can be customized based on cable section and insulation diameter.