17.5kV Cold-Shrinkable Indoor Termination

Product Descriptions
  • Premolded stress cone with geometric design and combine with sufficient interface pressure ensures effective electric field control and long-term reliability;

  • With sufficient electrical margin;

  • Installation requires no specialized tools, heating, or filling;

  • Can be installed vertically, at an inclined (≤30°) position;

  • Can be energized immediately after installation.

Contact us

Product Details

Application

•  Connect cable to overhead line/copper busbar.


Compatible Cables

• Cable Type: XLPE or other polymer-insulated, single-core copper/aluminum conductor MV power cable;

• Metallic Screen: Copper tape, Copper wires, Al wires, Al foil tape and etc.


Product Application Standards
Applicable standards: IEC 60502-4,GB/T 12706.4.


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

8.7/15 (17.5) kV

Rated Voltage (U₀ / U)

8.7/15kV

Highest System Voltage (Uₘ)

17.5 kV

Partial Discharge Test (pC)

At 1.73 U₀: no detectable PD above specified sensitivity

Power Frequency Withstand Voltage (KV)

At 4.5 U₀ for 5 min, no breakdown or flashover

Lightning Impulse Level(KV)

95

Creepage Distance ( mm)

≥440

Pollution Level

Height( mm)

500

Net Weight (Excluding Cable)(kg)

~1

 

Optional Solutions
• Creepage distance can be increased accordingly for high-altitude areas;
• The lug between the cable and terminal could be crimp or mechanical type.


Operating Conditions
• Ambient Temperature: -45°C to 45°C
• Installed indoor or inside electrical cabinet;
• Normal Altitude: ≤ 2000 meters (For higher altitude areas, bigger creepage distance should be selected based on the specific conditions).


Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Indoor with dry and clean environment, keep sealing and avoid ≥4 layers overlap.

Available Termination Selection (Recommended by Cable Insulation Diameter)

Voltage Level(kV)

Product Type

Conductor Size Range(mm²)

Cable Insulation Diameter(mm)

8.7/15/17.5

NLS- 8.7/15-1x25~50

25~50

16.4~18.5

8.7/15/17.5

NLS- 8.7/15-1x70~120                        

70~120

20.2~23.2

8.7/15/17.5

NLS- 8.7/15-1x150~240     

150~240

24.8~28.8

8.7/15/17.5

NLS- 8.7/15-1x300~400     

300~400

30.8~34

8.7/15/17.5

NLS- 8.7/15-1x500~630     

500~630

36.8~40.2

Note:It can be customized based on cable section and insulation diameter if the Termination's specification is outside the above ranges.