Premolded stress cone with geometric design and combine with sufficient interface pressure ensures effective electric field control and long-term reliability;
With sufficient electrical margin;
Installation requires no specialized tools, heating, or filling;
Can be installed vertically, at an inclined (≤30°) position;
Can be energized immediately after installation.
Application
• Connects cables to electrical cabinet or transformer.
Compatible Cables
• Cable Type: XLPE or other polymer-insulated, single or three cores copper/aluminum conductor MV power cables;
• Metallic Screen: Steel tape, Copper tape, Copper wires, Al wires, Al foil tape and etc.
Product Application Standards
• Applicable standards: IEC 60099-4,GB/T 11032;
• Interface standard :EN50180 - EN50181.
Optional Solutions
The length of the grounding wire can be customized
Operating Conditions
• Ambient Temperature: -45°C to 45°C
• Installation altitude: no limitation.
Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Indoor with dry and clean environment, keep sealing and avoid ≥4 layers overlap.
Aailable Termination Selection (Recommended by Cable Insulation Diameter)
Product Type | Ur(kV) | Uc(kV) | In(kA) | LIPL.(8/20uS) Ups (kV) | 1mA UrefDC |
CBB10-15/40.5 | 15 | 12 | 5 | 40.5 | ≥21.8 |
CBB10-15/45.6 | 15 | 12 | 5 | 45.6 | ≥23 |
CBB15-17/45 | 17 | 13.6 | 5 | 45 | ≥24 |
CBB15-17/50 | 17 | 13.6 | 5 | 50 | ≥25 |
CBB20-26/72 | 26 | 20.8 | 5 | 72 | ≥37 |
CBB30-34/85 | 34 | 27.2 | 5 | 85 | ≥48 |
CBB30-34/95 | 34 | 27.2 | 5 | 95 | ≥48 |
CBB35-30/80 | 30 | 24 | 5 | 80 | ≥44 |
CBB35-51/125 | 51 | 40.8 | 5 | 125 | ≥73 |
CBB35-51/134 | 51 | 40.8 | 5 | 134 | ≥73 |
CBB20-26/66 | 26 | 20.8 | 5 | 66 | ≥37 |
Note:If the Termination’s specification is outside the above ranges can be customized based on cable section and insulation diameter.