Angelor (Jiangsu) Intelligent Electric co.,LTD.

Position:首页 > Products > ​High-voltage cable accessories catalogue

245kV Promolded Straight Joint

Product Descriptions
  • The premolded stress cone, designed using geometrical electric field control and combined with sufficient interface pressure, ensures uniform electric field distribution and long-term reliable operation;

  • Sufficient electrical safety design;

  • Heat-shrink tube combined with plumbing provides excellent sealing performance and environmental protection;

  • External grounding outlet design allows easy grounding connection and reliable sealing protection;

  • Proven and mature design with extensive successful service experience.

Contact us

Product Details

Application

• Designed for the connection of high-voltage power cables; 

• Suitable for various installation conditions, including underground tunnels, direct burial installations (protective FRP box recommended), and installation on cable racks or supports;

• Applicable for cross-bonding earthing, protective earthing, or direct earthing in long-distance HV cable systems.


Compatible Cables

• Cable type: XLPE or other polymer-insulated, single-core copper/aluminum conductor HV power cables;

• Metallic Screen: Aluminum sheath, lead sheath, copper wire + aluminium copolymer tape, etc.


Product Application Standards

Applicable standards: IEC 62067, GB/T 18890.


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

127/220 (245) kV

Rated Voltage (U₀ / U)

127/220kV

Highest System Voltage (Uₘ)

245 kV

Partial Discharge Test /pCAt 1.5 U₀: no detectable PD above the specified sensitivity

Power Frequency Withstand Voltage /kV

At 2.0 U0 for 30 min, no breakdown or flashover

Lightning Impulse Level /kV

1050

Overall Dimensions (L × Ø) /mm

2200*540

Net Weight (excluding cable) /kg

160

 

Optional Solutions

• Conductor connection between cables by crimping or mechanical connector;

• Optional protective FRP box according to the site requirement;

• Optional fiber optic outlet design;

• Different cable sections connection can be matched according to the sleeve’s using range.


Operating Conditions

• Ambient temperature: ‒55 °C to +45 °C;

• Installation altitude: No limitation


Storage Conditions

• Recommended storage temperature: 10–25 °C

• Storage environment: Indoor, sealed, clean, dry, and protected from heavy load.

Insulated Joint Selection Guide(Recommended selection based on cable insulation diameter)

Voltage Level(kV)

Product   Type

Conductor   Size Range (mm²)

Cable   Insulation Diameter (mm)

Protective   Housing

127/220/245

YJJTI0 127/220

240~2500

81.5~114.5

Copper/ AL case

127/220/245

YJJTI1 127/220

240~2500

81.5~114.5

Copper/AL case + FRP protection box+ sealing compound

127/220/245

YJJTI2 127/220 

240~2500

81.5~114.5

Copper /AL box+sealing compound

Note:If the Termination’s specification is outside the above ranges can be customized based on cable section and insulation diameter.

  