Angelor (Jiangsu) Intelligent Electric co.,LTD.

Position:首页 > Products > ​High-voltage cable accessories catalogue

72.5~170kV Composite insulator outdoor termination

Product Descriptions
  • Premolded stress cone with geometric design,combined with sufficient interface pressure ensures effective electric field control and long-term reliability;

  • Wtih sufficient electrical safety desgin;

  • Using polyisobutylene insulating oil matched with the silicone rubber stress cone, fully ensuring the long-term insulation performance of the product;

  • The product is lightweight, easy to install, and poses an extremely low risk of damage to surrounding equipment during operation;

  • Mature design with extensive successful operational experience.

Contact us

Product Details

Application

•  Connects cables to overhead lines/copper busbars


Compatible Cables

• Cable Type: XLPE or other polymer-insulated, single-core copper/aluminum conductor HV power cables.

• Metallic Screen: Aluminum sheath, lead sheath, copper wire + aluminium copolymer tape, etc.


Product Application Standards
Applicable standards: IEC 60840, GB/T 11017.


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

38/66(72.5) kV

64/110 (126) kV

76/132(145)kV

87/150 (170) kV

Rated Voltage (U₀/U)

38/66kV

64/110kV

76/132kV

87/150 kV

Highest System Voltage (Uₘ)

72.5 kV

126 kV

145kV

170kV

Partial Discharge Test /pC

At 1.5 U₀: no detectable PD above specified sensitivity

Power Frequency Withstand Voltage /kV

At 2.0 U₀ for 30 min, no breakdown or flashover

Lightning Impulse Level /kV

325

550

650

750

Creepage Distance /mm

≥4050

Pollution Level

Height /mm

1980

1980

1980

2400

Net Weight (Excluding Cable) / kg

~120

~140

~140

~160

 

Optional Solutions

• Products with increased creepage distance for high-altitude areas;

• Crimping or mechanical connection method between the outgoing rod and cable conductor;
• Optical fiber port lead-out design.

• Lower temerature(-60℃) O ring can be selected to meet special circumstance.


Operating Conditions
• Ambient Temperature: -55°C to 45°C
• Installed on outdoor platforms or vertical towers, including power stations and in lines and so on; 

• Installation altitude: ≤2000 meters (For high-altitude areas, products with increased creepage distance should be selected based on specific conditions).


Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Storage Environment: Indoor, sealed, clean, dry, and protected from heavy pressure.

Available Termination Selection (Recommended by Cable Insulation Diameter

Voltage Level(kV)

Product Type

Conductor Size Range(mm²)

Cable Insulation Diameter(mm)

38/66/72

YJZWY4 38/66

300~2000

50~87

64/110/126

YJZWY4 64/110

240~1600

50~87

76/132/145

YJZWY4 76/132

240~1400

50~87

87/150/170

YJZWFY4 87/150

240~1600

50~87

Note:If the Termination’s specification is outside the above ranges can be customized based on cable section and insulation diameter.