Angelor (Jiangsu) Intelligent Electric co.,LTD.

Position:首页 > Products > ​High-voltage cable accessories catalogue

245kV Porcelain insulator outdoor termination

Product Descriptions
  • Premolded stress cone with geometric design,combined with sufficient interface pressure ensures effective electric field control and long-term reliability;

  • Wtih sufficient electrical safety desgin;

  • The high-strength porcelain insulator has excellent resistance to ultraviolet rays and self-cleaning capabilities;

  • Using polyisobutylene insulating oil matched with the silicone rubber stress cone, fully ensuring the long-term insulation performance of the product;

  • Mature design with extensive successful operational experience.

Contact us

Product Details

Application

•  Connects cables to overhead lines/copper busbars


Compatible Cables

• Cable Type: XLPE or other polymer-insulated, single-core copper/aluminum conductor HV power cables.

• Metallic Screen: Aluminum sheath, lead sheath, copper wire + aluminium copolymer tape, etc.


Product Application Standards
Applicable standards: IEC 62067, GB/T 18890.

 

Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

127/220 (245) kV

Rated Voltage (U₀ / U)

127/220kV

Highest System Voltage (Uₘ)

245 kV

Partial Discharge Test /pC

At 1.5 U₀: no detectable PD above specified sensitivity

Power Frequency Withstand Voltage /kV

At 2.0 U0 for 30 min, no breakdown or flashover

Lightning Impulse Level /kV

1050

Creepage Distance /mm

≥9300

Pollution Level

Height /mm

3150

Net Weight (Excluding Cable) / kg

~350

  

Optional Solutions
• Products with increased creepage distance for high-altitude areas;
• Crimping or mechanical connection method between the top connector and cable conductor;

• Optical fiber lead-out design.

• Lower temperature(-60℃) O ring can be selected to meet special circumstance.


Operating Conditions
• Ambient Temperature: -55°C to 45°C
• Installed on outdoor platforms or towers,includes in areas with few people and equipment, such as at the seaside or with severe pollution areas;

• Installation altitude: ≤ 2000 meters (For high-altitude areas, products with increased creepage distance should be selected based on specific conditions).


Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Storage Environment: Indoor, sealed, clean, dry, and protected from heavy pressure.

Available Termination Selection (Recommended by Cable Insulation Diameter

Voltage Level(kV)

Product Type

Conductor Size Range(mm²)

Cable Insulation Diameter(mm)

127/220/245

YJZWCC4 127/220

240~2500

81.5~114.5

Note:If the Termination’s specification is outside the above ranges can be customized based on cable section and insulation diameter.

Product Recommendation

Copyright © 2026 Angelor (Jiangsu) Intelligent Electric co.,LTD.

Privacy Policy