72.5~170kV Dry-type GIS Termination

Product Descriptions
  • Premolded stress cone with geometric design and uniform interfacial pressure from the spring compression system ensures effective electric field control and long-term reliability;

  • Sufficient electrical safety design;

  • Interface dimensions fully comply with the latest IEC and GB standards;

  • Dry-type, fully sealed top design for easy installation and elimination of gas leakage risk;

  • The epoxy insulator (GIS plug-in part) can be pre-installed in the GIS enclosure (with sealing insert or sealing plate) before shipment, allowing factory electrical testing together with the GIS equipment;

  • Extension rod design allows flexible configuration between short-type and long-type terminations;

  • Proven design with extensive service experience, ensuring high operational reliability.

Contact us

Product Details

Application
• Connects cables to high-voltage switch gear.


Compatible Cables

• Cable Type: XLPE or other polymer-insulated, single-core copper/aluminum conductor HV power cables; 

• Metallic Screen: Aluminum sheath, lead sheath, copper wire + aluminium copolymer tape, etc.


Product Application Standards

Applicable standards: IEC 60840,GB/T 11017,IEC 62271-209, GB/T 22381.


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

38/66(72.5) kV

64/110(126) kV

76/132(145)kV

87/150(170) kV

Rated Voltage (U₀/U)

38/66kV

64/110kV

76/132kV

87/150 kV

Highest System Voltage (Uₘ)

72.5 kV

126 kV

145kV

170kV

Partial Discharge Test /pC

At 1.5 U₀: no detectable PD above specified sensitivity

Power Frequency Withstand Voltage /kV

At 2.0 U₀ for 30 min, no breakdown or flashover

Lightning Impulse Level /kV

325

550

650

750

Overall Height L5/mm

310/583

470/757

470/757

470/757

Net Weight (Excluding Cable) / kg

65

 

Optional Solutions

• End bell to Metallic Sheath Connection: plumbing or mechanical connection;

• Connection between top connector and cable conductor by crimping or mechanical connector; 

• Plug-in type or assembly type termination is available, supporting multi-angle installation; 

• Optional flange surge arrester can be choosed (with L shape copper link);

• Optional fiber optic outlet design.


Operating Conditions

• Ambient temperature: –55 °C to +45 °C

• Installation: Indoor or outdoor substations, connected to Transformer equipment; 

• Installation altitude: No limitation.


Storage Conditions

• Recommended storage temperature: 10–25 °C

• Storage Environment: Indoor, sealed, Clean, dry, and protected from heavy pressure. 

Available Termination Selection (Recommended by Cable Insulation Diameter)

Voltage Level(kV)

Product Type

Standard (L5) (mm)

Conductor Size Range(mm²)

Cable Insulation Diameter(mm)

38/66/72.5

YJZGGS 38/66

310

300~2000

50~87

38/66/72.5

YJZGGL 38/66

583

300~2000

50~87

64/110/126

YJZGGS 64/110  

470

240~1600

50~87

64/110/126

YJZGGL 64/110

757

240~1600

50~87

76/132/145

YJZGGS 76/132

470

240~1600

50~87

76/132/145

YJZGGL 76/132

757

240~1600

50~87

87/150/170

YJZGGS 87/150  

470

240~1600

50~87

87/150/170

YJZGGL 87/150

757

240~1600

50~87

Note:If the Termination’s specification is outside the above ranges can be customized based on cable section and insulation diameter.


Size

Voltage Level (kV)

Conductor Size Range(mm²)

L5[mm]

t2[mm]

M1xt1

Long

Short

38/66/72.5

240 ~ 1600 (Cu/Al)

583

310

270

M10x∅80

64/110/126

240 ~ 1600 (Cu/Al)

757

470

320

M10x∅80

76/132/145

240 ~ 1600 (Cu/Al)

757

470

320

M10x∅80

87/150 /170

240 ~ 1600 (Cu/Al)

757

470

320

M10x∅80


Product Recommendation