Angelor (Jiangsu) Intelligent Electric co.,LTD.

Position:首页 > Products > Medium-voltage cable accessories catalogue

12kV Cold-Shrinkable Outdoor Termination

Product Descriptions
  • Premolded stress cone with geometric design and combine with sufficient interface pressure ensures effective electric field control and long-term reliability;

  • With sufficient electrical margin;

  • Installation requires no specialized tools, heating, or filling;

  • Can be installed vertically, at an inclined (≤30°) position;

  • Can be energized immediately after installation.

Contact us

Product Details

Application

•  Connect cable to overhead line/copper busbar.


Compatible Cables

• Cable Type: XLPE or other polymer-insulated, single-core copper/aluminum conductor MV power cables; 

• Metallic Screen: Copper tape, Copper wires, Al wires, Al foil tape and etc.


Product Application Standards
Applicable standards: IEC 60502-4,GB/T 12706.4.


Technical Parameters

ItemTechnical Specifications

Voltage Level(kV)

6/10 (12) kV

Rated Voltage (U₀ / U)

6/10 kV

Highest System Voltage (Uₘ)

12 kV

Partial Discharge Test (pC)

At 1.73 U₀: no detectable PD above specified sensitivity

Power Frequency Withstand Voltage (KV)

At 4.5 U₀ for 5 min, no breakdown or flashover

Lightning Impulse Level(KV)

75

Creepage Distance ( mm)

≥545

Pollution Level

Height( mm)

500

Net Weight (Excluding Cable)(kg)

~1.1

 

Optional Solutions
• Products with increased creepage distance for high-altitude areas;
• The connection between the cable lug and the cable conductor employs crimping or mechanical methods.


Operating Conditions
• Ambient Temperature: -45°C to 45°C
• Installed on outdoor platforms or vertical towers, and so on;

• Installation altitude: ≤ 2000 meters (For higher altitude areas, products with increased creepage distance should be selected based on specific conditions).


Storage Conditions
• Optimal Storage Temperature: 10°C to 25°C
• Indoor with dry and clean environment, keep sealing and avoiding ≥4 layers overlap.

Available Termination Selection (Recommended by Cable Insulation Diameter)

Voltage Level(kV)

Product Type

Conductor Size Range(mm²)

Cable Insulation Diameter(mm)

6/10/12

WLS- 6/10-1x25~50

25~50

16.4~18.5

6/10/12

WLS- 6/10-1x70~120

70~120

20.2~23.2

6/10/12

WLS- 6/10-1x150~240

150~240

24.8~28.8

6/10/12

WLS- 6/10-1x300~400

300~400

30.8~34

6/10/12

WLS- 6/10-1x500~630

500~630

36.8~40.2

Note:It can be customized based on cable section and insulation diameter if the Termination's specification is outside the above ranges.