● The main insulation of the product is an integral premolded constructure. The high-voltage shield, sleeve and insulating parts are injected into one piece. The constructure is simple and easy to be installed.
● The outer shielding layer of the main insulator is injected with semi-conductive silicone rubber to avoid the shortcoming that the sprayed surface is easy to damage.
● The housing adopts high-strength copper protection case with high mechanical strength and good sealing performance.
● The main insulation of the product is an integral premolded constructure. The high-voltage shield, sleeve and insulating parts are injected into one piece. The constructure is simple and easy to be installed.
● The outer shielding layer of the main insulator is injected with semi-conductive silicone rubber to avoid the shortcoming that the sprayed surface is easy to damage.
● The housing adopts high-strength copper protection case with high mechanical strength and good sealing performance.
Product introduction: 110kV integral prefabricated intermediate joint product introduction.pdf
Structure diagram: 110kV integral prefabricated intermediate insulation joint structure diagram.pdf
Structure diagram: 110kV integral prefabricated intermediate straight-through joint structure diagram.pdf
Product introduction: 110kV integral prefabricated intermediate joint product introduction.pdf
Structure diagram: 110kV integral prefabricated intermediate insulation joint structure diagram.pdf
Structure diagram: 110kV integral prefabricated intermediate straight-through joint structure diagram.pdf
| Technical Specifications | |
| Area Of Application | |
| Applicable cable cross-sections: | 240~1600 mm2 | 
| Max.system voltage: | 145 kV | 
| System rated frequency: | 50 Hz | 
| Elevation: | ≤2000 m | 
| Operation temperature: | -55 ℃~45 ℃ | 
| Cable Shield Style | Tape/wire/corrugated Al | 
| Design Data | |
| Max.exteral dimensions(diameter × length) | ∅270 × 2020 mm | 
| Weight(excluding cable) | 70 kg / 154.3 lbs | 
| Anticorrosive coating | Heat shrink tubing | 
| Protective measures | Three options:heat shrink tubing, protective copper shell and FRP shell | 
| System of a laying joints | Tunnel | 
| Storage temperature | 0 ℃~35 ℃ | 
| Electrical Test | |
| Electrical Type Test(IEC 60840) | |
| Heating cycle voltage | 152 kV | 
| Partial discharge test at ambient and elevated temperatures | No detctable discharge exceeding the declared sensitivity (114kV, 3.6pC) | 
| Lighting impulse voltage 1.2 ㎲/50 ㎲ | 650 kV | 
| Electrical Routine Test(IEC 60840) | |
| AC withstand voltage | 190 kV | 
| Partial discharge test | No detctable discharge exceeding the declared sensitivity (114kV, 3.6pC) | 
| Technical Specifications | |
| Area Of Application | |
| Applicable cable cross-sections: | 240~1600 mm2 | 
| Max.system voltage: | 145 kV | 
| System rated frequency: | 50 Hz | 
| Elevation: | ≤2000 m | 
| Operation temperature: | -55 ℃~45 ℃ | 
| Cable Shield Style | Tape/wire/corrugated Al | 
| Design Data | |
| Max.exteral dimensions(diameter × length) | ∅270 × 2020 mm | 
| Weight(excluding cable) | 70 kg / 154.3 lbs | 
| Anticorrosive coating | Heat shrink tubing | 
| Protective measures | Three options:heat shrink tubing, protective copper shell and FRP shell | 
| System of a laying joints | Tunnel | 
| Storage temperature | 0 ℃~35 ℃ | 
| Electrical Test | |
| Electrical Type Test(IEC 60840) | |
| Heating cycle voltage | 152 kV | 
| Partial discharge test at ambient and elevated temperatures | No detctable discharge exceeding the declared sensitivity (114kV, 3.6pC) | 
| Lighting impulse voltage 1.2 ㎲/50 ㎲ | 650 kV | 
| Electrical Routine Test(IEC 60840) | |
| AC withstand voltage | 190 kV | 
| Partial discharge test | No detctable discharge exceeding the declared sensitivity (114kV, 3.6pC) |